Description
The transmitter can be set for latching or non-latching alarm, and normally energized or normally deenergized operation.
Key Features
- 5 Amp Relays @ 30VAC/DC | 24 VAC or VDC Power | NEMA 4 Enclosure
- Detection Within 5 Seconds with Local LED Alarm Indication
Specifications
- Power: 24VAC/VDC +/- 10%
- Wiring: Flex Connector or Liquid-Tight Fitting | Relays Up to 6 wires for Alarm Contacts | Transmitter 2 wires for Power
- Mounting: Lays in the pan with industrial adhesive tape or attached to the pan edge with screws
- Sensor: Standard Attached SS probe w/ adjustable depth screw from .063” to .84” (OR) | Remote Long Line Wire Sensor (Rope), Plenum Rated Detects 1/8”of water over the full length 10 length.
- Detector Transmitter: Alarm Contacts: Two SPDT, 5A relay outputs* | Indication 1 Green Power LED, 1 Red Alarm LED | Reset Action If latching, local push button or power interrupt
- Termination: Terminal strip, 12 to 24 AWG
- Enclosure Ratings: Remote Sensor Submersible, with FEP plenum-rated, waterproof cable | Detector NEMA 4 Box
- Ambient: Rope Sensor 32 to 167ºF (0 to 75ºC), 0 to 95%RH, Non-condensing | Attached -40 to 185ºF (-40 to 85ºC), 0 to 95%RH, Non-condensing
- Materials: Sensor: Stainless Steel
- Agency: RoHS, UL94V-0 , UV-rated in Enclosure
* Latching Relay stays in alarm until manually reset or power is cycled | Adjustable Detection Level with Bottom or Pan Edge Mounting